The QJ12-25 is a dual-float Buchholz relay (gas-actuated relay) installed in the piping between the transformer tank and the conservator. It provides internal-fault protection by detecting two independent conditions: the gradual accumulation of gas generated by minor faults, and the sudden oil flow surge caused by severe arcing faults.
Unlike single-float designs that rely on a mechanical flap, the QJ12-25 uses two separate floats, each equipped with its own mercury-tilt switch. The upper float responds to gas accumulation and issues an alarm; the lower float responds to rapid oil displacement and triggers tripping. This dual-stage, float-only architecture offers high sensitivity, a simple structure, and reliable two-level protection without any oil-flow baffle.
Dual-Float Working Principle
Normal operation: Both floats are immersed in oil and held in their upper positions; both alarm and trip contacts remain open.
Minor / incipient fault (alarm): Decomposition gas collects at the top of the relay body, lowering the oil level. The upper float drops and its mercury switch closes to activate an alarm signal (e.g., at 200-250 cm³ of gas).
Severe internal fault (trip): A large volume of gas and rapid oil flow forces the oil level down sharply. The lower float drops and its mercury switch closes to trip and disconnect the transformer (oil flow surge corresponding to roughly 0.8-1.2 m/s).
2. Model Designation
2.1 Model and Description
Code
Meaning
QJ
Gas-actuated relay (Buchholz relay)
12
Design series (dual-float type)
25
Connection diameter DN25 (pipe / flange size)
2.2 Construction
Cast aluminium alloy housing, hermetically sealed against moisture and suitable for outdoor service.
Upper float (alarm): tilts as gas accumulates, actuating one mercury-tilt switch for alarm / signal output.
Lower float (trip): responds to rapid oil flow / oil-level drop, actuating a second mercury-tilt switch for tripping.
Two independent mercury-tilt switches (SPDT), one per float, for reliable alarm and trip contacts.
Transparent inspection window for visual check of oil level, float position and gas accumulation.
Top vent / test valve for manual gas release and functional testing without dismantling the relay.